[Analysis of noise reduction measures in a noise workshop handover control room].
Zhonghua Lao Dong Wei Sheng Zhi Ye Bing Za Zhi
; 41(5): 379-382, 2023 May 20.
Article
in Zh
| MEDLINE
| ID: mdl-37248087
Objective: To explore the sound insulation, sound absorption and other noise reduction transformation methods in a noise workshop handover control room. Methods: In December 2021, through the occupational health investigation and on-site testing of the handover control room of a noise workshop, the causes of excessive noise were analyzed, and the transformation design scheme to reduce noise was proposed and the effect was analyzed. Results: Before the transformation, the peak frequency band noise intensity of the noise workshop handover control room was 112.8 dB (A), and the peak frequency was 1000 Hz. After noise reduction, the theoretical calculated control value was 61.0 dB (A), and the measured noise intensity was 59.8 dB (A) . Conclusion: The noise intensity of the handover control room is reduced after noise reduction, which is in line with the contact limit requirements of the control room in GBZ 1-2010 "Hygienic Standards for the Design of Industrial Enterprises", and has reference significance for noise control engineering.