Application and analysis of a model based controller for cooling towers in compression chiller plants.
Sawant, Parantapa; Ho, Eric; Pfafferott, Jens.
Afiliação
  • Sawant P; Institute of Energy Systems Technology (INES), Offenburg University of Applied Sciences, Offenburg, Germany.
  • Ho E; Department of Mechanical and Aerospace Engineering, Carleton University, Ottawa, Canada.
  • Pfafferott J; Institute of Energy Systems Technology (INES), Offenburg University of Applied Sciences, Offenburg, Germany.
Heliyon ; 6(2): e03249, 2020 Feb.
Article em En | MEDLINE | ID: mdl-32072036
ABSTRACT
Cooling towers or recoolers are one of the major consumers of electricity in a HVAC plant. The implementation and analysis of advanced control methods in a practical application and its comparison with conventional controllers is necessary to establish a framework for their feasibility especially in the field of decentralised energy systems. A standard industrial controller, a PID and a model based controller were developed and tested in an experimental set-up using market-ready components. The characteristics of these controllers such as settling time, control difference, and frequency of control actions are compared based on the monitoring data. Modern controllers demonstrated clear advantages in terms of energy savings and higher accuracy and a model based controller was easier to set-up than a PID.
Palavras-chave

Texto completo: 1 Coleções: 01-internacional Base de dados: MEDLINE Tipo de estudo: Prognostic_studies Idioma: En Revista: Heliyon Ano de publicação: 2020 Tipo de documento: Article

Texto completo: 1 Coleções: 01-internacional Base de dados: MEDLINE Tipo de estudo: Prognostic_studies Idioma: En Revista: Heliyon Ano de publicação: 2020 Tipo de documento: Article