Your browser doesn't support javascript.
loading
A modular neural network scheme applied to fault diagnosis in electric power systems.
Flores, Agustín; Quiles, Eduardo; García, Emilio; Morant, Francisco; Correcher, Antonio.
Afiliação
  • Flores A; Área de Control Peninsular, CFE, Instituto Tecnológico de Mérida, Departamento de Eléctrica, C10 No. 312-A Fraccionamiento Gonzalo Guerrero, 97118 Mérida, YUC, Mexico.
  • Quiles E; Departamento de Ingeniería de Sistemas y Automática, Universitat Politècnica de València, C. Vera 14, 46022 Valencia, Spain.
  • García E; Departamento de Ingeniería de Sistemas y Automática, Universitat Politècnica de València, C. Vera 14, 46022 Valencia, Spain.
  • Morant F; Departamento de Ingeniería de Sistemas y Automática, Universitat Politècnica de València, C. Vera 14, 46022 Valencia, Spain.
  • Correcher A; Departamento de Ingeniería de Sistemas y Automática, Universitat Politècnica de València, C. Vera 14, 46022 Valencia, Spain.
ScientificWorldJournal ; 2014: 176463, 2014.
Article em En | MEDLINE | ID: mdl-25610897
ABSTRACT
This work proposes a new method for fault diagnosis in electric power systems based on neural modules. With this method the diagnosis is performed by assigning a neural module for each type of component comprising the electric power system, whether it is a transmission line, bus or transformer. The neural modules for buses and transformers comprise two diagnostic levels which take into consideration the logic states of switches and relays, both internal and back-up, with the exception of the neural module for transmission lines which also has a third diagnostic level which takes into account the oscillograms of fault voltages and currents as well as the frequency spectrums of these oscillograms, in order to verify if the transmission line had in fact been subjected to a fault. One important advantage of the diagnostic system proposed is that its implementation does not require the use of a network configurator for the system; it does not depend on the size of the power network nor does it require retraining of the neural modules if the power network increases in size, making its application possible to only one component, a specific area, or the whole context of the power system.
Assuntos

Texto completo: 1 Coleções: 01-internacional Base de dados: MEDLINE Assunto principal: Fontes de Energia Elétrica / Redes Neurais de Computação / Eletricidade Tipo de estudo: Diagnostic_studies Limite: Humans Idioma: En Revista: ScientificWorldJournal Assunto da revista: MEDICINA Ano de publicação: 2014 Tipo de documento: Article País de afiliação: México

Texto completo: 1 Coleções: 01-internacional Base de dados: MEDLINE Assunto principal: Fontes de Energia Elétrica / Redes Neurais de Computação / Eletricidade Tipo de estudo: Diagnostic_studies Limite: Humans Idioma: En Revista: ScientificWorldJournal Assunto da revista: MEDICINA Ano de publicação: 2014 Tipo de documento: Article País de afiliação: México