J Formos Med Assoc ; 122(2): 91-97, 2023 Feb.
Artigo em Inglês | MEDLINE | ID: mdl-36476674

RESUMO

This mini-review provides the practice guideline recommendations for ventilation of remodeled negative-pressure isolation wards for COVID-19 Patients. Remodeled "quasi-negative-pressure" isolation wards had been proved a feasible, inexpensive, safe, and effective measure to contain nosocomial outbreaks. We should first determine the minimum required ventilation volume of an isolation ward based on the severity of COVID-19 patients. Mechanical ventilation remains the mainstay for achieving the requirement, while the assistance of recirculation is also helpful. Beyond adequate ventilation volume, the "clean to less-clean" directional airflow remains the golden rule for the solution of indoor ventilation. The virus-laden exhaust should be treated with HEPA/UV device or be kept away from living organisms, buildings, and air inlets.


Assuntos
COVID-19 , Humanos , Isolamento de Pacientes , Ventilação , Hospitais , Surtos de Doenças