RESUMO
This study seeks to analyze how the degree of carbonation and the application of waterproofing and anticorrosive materials affect carbonation in water reservoirs among the water treatment facilities managed by the Seoul Metropolitan Government. To guarantee similarity of the experimental group, 42 highly similar water reservoirs were selected from among the water supply reservoirs currently in operation in Seoul. On-site carbonation assessments were performed in order to derive the carbonation rate coefficients. In the water reservoirs with applied waterproofing and anticorrosive materials immediately after public service, the upper and lower limits were D = 1.13t and D = 0.29t, respectively, whereas those of the water reservoir applied with waterproofing and anticorrosive materials after 15 years of service life were D = 1.89t and D = 0.94t, respectively. The comparative analysis showed that the rate of reduction in the carbonation rate was about 10.4% to 16.8% in the water reservoirs applied with waterproofing and anticorrosive methods after 15 years of service life. However, reduction in the carbonation rate was about 46.4% to 74.3% in the water reservoirs applied with waterproofing and anticorrosive methods at the initial stage of service life. It was confirmed that the early application of waterproofing and anticorrosive materials is effective in suppressing carbonation of concrete water reservoir structures.