The utility of intensified environmental surveillance for pathogenic moulds in a stem cell transplantation ward during construction work to monitor the efficacy of HEPA filtration.
Nihtinen, A; Anttila, V-J; Richardson, M; Meri, T; Volin, L; Ruutu, T.
Afiliación
  • Nihtinen A; Department of Medicine, Helsinki University Central Hospital, Helsinki, Finland. anne.nihtinen@hus.fi
Bone Marrow Transplant ; 40(5): 457-60, 2007 Sep.
Article en En | MEDLINE | ID: mdl-17589532
ABSTRACT
A 12-week environmental study was performed to ensure that the patient rooms of an SCT ward with high-efficiency particulate air (HEPA) filtration remained uncontaminated by moulds during close-by construction work. The sampling included measuring the ventilation channel pressure, particle count measurements, air sampling, settled dust analysis and fungal cultures from the oral and nasal cavities of the patients. No changes in the air pressure occurred. Median particle counts in patient rooms were 63-420 particles/l. The mean particle count of the outside air was 173,659 particles/l. Patient room air samples were negative for aspergilli in 32 of 33 cases. All samples of the outside air were positive for moulds. Aspergillus fumigatus was isolated at the beginning of excavation works at the construction area and in two of 33 dust samples from patient rooms. All 70 nasal samples were negative. Of 35 mouth samples, one sample was positive for A. niger in a patient with a previously diagnosed aspergillus infection. During a median follow-up of 214 days, no invasive aspergillus infections were diagnosed in the 55 patients treated during the construction period. In conclusion, the HEPA filters seemed to have performed well in preventing an aspergillosis outbreak.
Asunto(s)
Buscar en Google
Banco de datos: MEDLINE Asunto principal: Ventilación / Contaminación del Aire Interior / Trasplante de Células Madre / Arquitectura y Construcción de Instituciones de Salud / Hongos / Unidades Hospitalarias Tipo de estudio: Screening_studies Límite: Humans Idioma: En Año: 2007 Tipo del documento: Article
Buscar en Google
Banco de datos: MEDLINE Asunto principal: Ventilación / Contaminación del Aire Interior / Trasplante de Células Madre / Arquitectura y Construcción de Instituciones de Salud / Hongos / Unidades Hospitalarias Tipo de estudio: Screening_studies Límite: Humans Idioma: En Año: 2007 Tipo del documento: Article