Your browser doesn't support javascript.
loading
Acoustic Sensors for Monitoring and Localizing Partial Discharge Signals in Oil-Immersed Transformers under Array Configuration.
Wang, Yang; Zhao, Dong; Jia, Yonggang; Wang, Shaocong; Du, Yan; Li, Huaqiang; Zhang, Bo.
Afiliación
  • Wang Y; School of Electronics and Information, Xi'an Polytechnic University, Xi'an 710048, China.
  • Zhao D; School of Electronics and Information, Xi'an Polytechnic University, Xi'an 710048, China.
  • Jia Y; School of Electronics and Information, Xi'an Polytechnic University, Xi'an 710048, China.
  • Wang S; School of Electronics and Information, Xi'an Polytechnic University, Xi'an 710048, China.
  • Du Y; School of Electronics and Information, Xi'an Polytechnic University, Xi'an 710048, China.
  • Li H; State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University, Xi'an 710049, China.
  • Zhang B; School of Electronics and Information, Xi'an Polytechnic University, Xi'an 710048, China.
Sensors (Basel) ; 24(14)2024 Jul 20.
Article en En | MEDLINE | ID: mdl-39066101
ABSTRACT
Partial discharge (PD) is one of the major causes of insulation accidents in oil-immersed transformers, generating a large number of signals that represent the health status of the transformer. In particular, acoustic signals can be detected by sensors to locate the source of the partial discharge. However, the array, type, and quantity of sensors play a crucial role in the research on the localization of partial discharge sources within transformers. Hence, this paper proposes a novel sensor array for the specific localization of PD sources using COMSOL Multiphysics software 6.1 to establish a three-dimensional model of the oil-immersed transformer and the different defect types of two-dimensional models. "Electric-force-acoustic" multiphysics field simulations were conducted to model ultrasonic signals of different types of PD by setting up detection points to collect acoustic signals at different types and temperatures instead of physical sensors. Subsequently, simulated waveforms and acoustic spatial distribution maps were acquired in the software. These simulation results were then combined with the time difference of arrival (TDOA) algorithm to solve a system of equations, ultimately yielding the position of the discharge source. Calculated positions were compared with the actual positions using an error iterative algorithm method, with an average spatial error about 1.3 cm, which falls within an acceptable range for fault diagnosis in transformers, validating the accuracy of the proposed method. Therefore, the presented sensor array and computational localization method offer a reliable theoretical basis for fault diagnosis techniques in transformers.
Palabras clave

Texto completo: 1 Colección: 01-internacional Banco de datos: MEDLINE Idioma: En Revista: Sensors (Basel) Año: 2024 Tipo del documento: Article País de afiliación: China

Texto completo: 1 Colección: 01-internacional Banco de datos: MEDLINE Idioma: En Revista: Sensors (Basel) Año: 2024 Tipo del documento: Article País de afiliación: China