1.
Sci Rep ; 11(1): 21412, 2021 11 01.
Artículo en Inglés | MEDLINE | ID: mdl-34725386

RESUMEN

Ventilation, including fume hoods, consumes 40-70% of the total energy used by modern laboratories. Energy-conscious fume hood usage-for example, closing the sash when a hood is unused-can significantly reduce energy expenditures due to ventilation. Prior approaches to promote such behaviors among lab users have primarily relied on passive feedback methods. In this work, we developed a low-cost fume hood monitoring device with active feedback to alert lab users when a fume hood is left open and unused. Using data collected by the building management system, we observed a 75.6% decrease in the average sash height after installation of these "Motion and Sash Height" (MASH) alarms, which would result in a reduction roughly equal to 43% of the annual carbon emissions of a typical American vehicle, for each fume hood. The MASH alarm presented here reduced energy costs by approximately $1,159 per year, per hood, at MIT.