1.
J Radiol Prot ; 41(4)2021 Dec 06.
Artículo en Inglés | MEDLINE | ID: mdl-33513588

RESUMEN

A study of the radon activity concentration was carried out at the School of Computer Science of 'Universidade da Coruña' (UDC, Spain). For this purpose, building location, the type of soil and the construction materials were analysed. Subsequently, the radon activity concentration was determined using two different techniques: measurement in situ with an on-site ionization chamber detector (short term) and measurement with trace detectors (long term). Based on the results obtained, and according with the Spanish Law (Spanish Official Bulletin-Boletín Oficial del Estado, of 21 December 2011, IS-33 Instruction), corrective works were performed, consisting on the installation of a forced ventilation system underneath the extent of the suspended floor in order to mitigate the high radon specific activity in the building. Four months and 3 years after the works, new measurements were carried out in order to verify the effectiveness of the new ventilation system, obtaining a decrease of the radon gas values ranging between 87% and 90%, which confirmed long term effectivity.


Asunto(s)
Contaminantes Radiactivos del Aire , Contaminación del Aire Interior , Monitoreo de Radiación , Radón , Contaminantes Radiactivos del Aire/análisis , Contaminación del Aire Interior/análisis , Computadores , Vivienda , Radón/análisis , Instituciones Académicas , España
SELECCIÓN DE REFERENCIAS