Use of carbon dioxide measurements to assess ventilation in an acute care hospital.
Am J Infect Control
; 50(2): 229-232, 2022 02.
Article
in En
| MEDLINE
| ID: mdl-34848292
Poorly ventilated indoor spaces pose a risk for airborne transmission of SARS-CoV-2. We measured carbon dioxide levels in a multiple areas in an acute care hospital to assess the adequacy of ventilation. Carbon dioxide levels remained below 800 parts per million in most areas but exceeded this level in a small conference room with 8 occupants, an office with 3 occupants, and a bathroom with 2 occupants. Measuring carbon dioxide levels could provide a simple means for healthcare facilities to assess the adequacy of ventilation.