Your browser doesn't support javascript.
loading
Validez de un método fotométrico de medición de partículas en aire para el control de quirófanos y otras salas de ambiente controlado en los hospitales / Validity of a photometric method of counting particles in air for control of operating rooms and clean rooms in hospitals
Uriel Latorre, B; Seoane Mato, D; Alves Pérez, M. T; Azuara García, M. J; García García, M. J; Blanco Rodríguez, A; Fernández de Armas, L; López Álvarez, S; Méndez Diéguez, M. C.
Afiliación
  • Uriel Latorre, B; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • Seoane Mato, D; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • Alves Pérez, M. T; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • Azuara García, M. J; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • García García, M. J; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • Blanco Rodríguez, A; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • Fernández de Armas, L; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • López Álvarez, S; Complexo Hospitalario Universitario de Ourense. Ourense. España
  • Méndez Diéguez, M. C; Complexo Hospitalario Universitario de Ourense. Ourense. España
Trauma (Majadahonda) ; 24(3): 195-199, jul.-sept. 2013. tab, ilus
Artículo en Español | IBECS | ID: ibc-115582
Biblioteca responsable: ES1.1
Ubicación: BNCS
RESUMEN

Objetivo:

Validar un sistema de medici¨®n fotom¨¦trica de part¨ªculas en aire para realizar los controles de bioseguridad ambiental de quir¨®fanos y otras salas de ambiente controlado en los hospitales. Material y m¨¦todos Se realizaron un total de 144 mediciones pareadas de aire, 88 en ocho quir¨®fanos con sistemas de ventilaci¨®n convencional y tres niveles de filtraci¨®n y 56 en nueve habitaciones sin instalaciones de ventilaci¨®n. Se midieron part¨ªculas de entre 0,1 a 10 ¦Ìm en mg/m3 por m¨¦todo fotom¨¦trico. Simult¨¢neamente, en cada sala se realiz¨® impacto de aire en placas de Petri con medio de cultivo mediante aparato aspirador de cabezal perforado, obteniendo tras cinco d¨ªas de incubaci¨®n recuento de unidades formadoras de colonias (UFC)/1000L. Finalmente se realiz¨® el c¨¢lculo de los puntos de corte ¨®ptimos para la medici¨®n de part¨ªculas mediante Curvas ROC para discriminar tres niveles de contaminaci¨®n.

Resultados:

El coeficiente de correlaci¨®n entre las dos mediciones fue 0,779 (p<0,001). Los puntos de corte fueron para 0 UFC. 0,015, para >=10 UFC, 0,037, y para >=100 UFC, 0,053. La sensibilidad para estos puntos fue de 95,83%,100% y 100%, y los ¨ªndices Kappa registraron 0,51, 0,88 y 0,75 respectivamente. Conclusi¨®n En nuestro estudio la correlaci¨®n entre las medidas es notable; la medici¨®n fotom¨¦trica de part¨ªculas puede ser una alternativa para llevar a cabo alguno de los controles rutinarios de bioseguridad (AU)
ABSTRACT

Objective:

Validate a photometric on-air particle measurement system in order to perform ambient bio-security checks in operating rooms and other clean rooms within hospitals. Material and

methods:

A total of 144 coupled air samples were performed, 88 in 8 different operating rooms with conventional ventilation systems and 3-level filtering and 56 in 9 different rooms without specific ventilation systems. Particles were measured in size between 0,1 to 10 ¦Ìm with the photometric system in mg/m3. Simultaneously in the rooms are performed the sampling air method with impact on culture media. Incubation period is 5 days and count is performed in colony-forming units (CFU/1000L). Finally, optimal cut-points in particles measure were calculated using ROC curves in order to discriminate the three different contamination levels.

Results:

Spearma´s correlation coefficient was 0,779 p<0,001. Sensitivity for cut-points in particle counting for the different contamination levels was 95,83% ,100% and 100% respectively, and the corresponding Kappa indexes were 0,51; 0,88 and 0,75.

Conclusion:

Correlation among measurements is notable. Particle measurement can be a worthy alternative for some of the routine bio-security checks (AU)
Asunto(s)
Buscar en Google
Colección: Bases de datos nacionales / España Contexto en salud: ODS3 - Meta 3D Fortalecer la capacidad de alerta temprana, reducción y gestión de riesgos sanitarios nacionales y globales / Agenda de Salud Sostenible para las Américas / ODS3 - Salud y Bienestar Problema de salud: Riesgos Biológicos / Objetivo 6: Sistemas de información para la salud / Meta 3.9: Reducir la cantidad de muertes producidas por químicos peligrosos y la contaminación del aire, agua y suelo Base de datos: IBECS Asunto principal: Quirófanos / Fotometría / Sistemas de Información en Quirófanos / Contención de Riesgos Biológicos Límite: Femenino / Humanos / Masculino Idioma: Español Revista: Trauma (Majadahonda) Año: 2013 Tipo del documento: Artículo Institución/País de afiliación: Complexo Hospitalario Universitario de Ourense/España
Buscar en Google
Colección: Bases de datos nacionales / España Contexto en salud: ODS3 - Meta 3D Fortalecer la capacidad de alerta temprana, reducción y gestión de riesgos sanitarios nacionales y globales / Agenda de Salud Sostenible para las Américas / ODS3 - Salud y Bienestar Problema de salud: Riesgos Biológicos / Objetivo 6: Sistemas de información para la salud / Meta 3.9: Reducir la cantidad de muertes producidas por químicos peligrosos y la contaminación del aire, agua y suelo Base de datos: IBECS Asunto principal: Quirófanos / Fotometría / Sistemas de Información en Quirófanos / Contención de Riesgos Biológicos Límite: Femenino / Humanos / Masculino Idioma: Español Revista: Trauma (Majadahonda) Año: 2013 Tipo del documento: Artículo Institución/País de afiliación: Complexo Hospitalario Universitario de Ourense/España
...