Your browser doesn't support javascript.
loading
Legionelosis en un establecimiento considerado de bajo riesgo de proliferación / Legionellosis in a site with low risk of proliferation
Pañella, Helena; Calzada, Núria; Beneyto, Vicente; Valero, Natalia; Gracia, José; Rodríguez, Pau.
Afiliação
  • Pañella, Helena; Direcció de Serveis de Vigilància Ambiental. Agència de Salut Pública de Barcelona. Barcelona. España
  • Calzada, Núria; Direcció de Serveis de Vigilància Ambiental. Agència de Salut Pública de Barcelona. Barcelona. España
  • Beneyto, Vicente; Direcció de Serveis de Vigilància Ambiental. Agència de Salut Pública de Barcelona. Barcelona. España
  • Valero, Natalia; Direcció de Serveis de Vigilància Ambiental. Agència de Salut Pública de Barcelona. Barcelona. España
  • Gracia, José; Direcció de Serveis de Vigilància Ambiental. Agència de Salut Pública de Barcelona. Barcelona. España
  • Rodríguez, Pau; Direcció de Serveis de Vigilància Ambiental. Agència de Salut Pública de Barcelona. Barcelona. España
Gac. sanit. (Barc., Ed. impr.) ; 24(6): 498-500, nov.-dic. 2010. ilus, tab
Artigo em Espanhol | IBECS | ID: ibc-97552
Biblioteca responsável: ES1.1
Localização: BNCS
RESUMEN
Ante tres casos de legionelosis asociados a un establecimiento balneario se inició la investigación para confirmar la fuente de infección, determinar el riesgo y controlarlo. Entre el 26 de noviembre de 2008 y el 16 de septiembre de 2009 se realizaron seis inspecciones, con toma de temperaturas y muestras de agua para el aislamiento de Legionella pneumophila en todos los puntos de la red de agua caliente sanitaria y en las piscinas climatizadas. Se confirmó la presencia de L. pneumophila del serogrupo 1 con el mismo patrón molecular que la cepa clínica en el circuito de agua caliente sanitaria (de bajo riesgo de proliferación). La tasa de ataque bruta fue del 0,34% (intervalo de confianza del 95% 0,09–0,94). Solo se obtuvieron muestras de agua sin presencia de L. pneumophila tras realizar cambios estructurales. Las temperaturas del agua entre 25 y 30°C, el estancamiento del agua y la exposición a primera hora de la mañana serían factores participantes en la agrupación de casos (AU)
ABSTRACT
After three cases of legionellosis associated with a spa were identified, an investigation was conducted to confirm the source of infection, determine the risk factors, and establish control measures. Between November 26, 2008 and September 16, 2009, six inspections were carried out, samples were collected for Legionella pneumophila isolation, and water temperature was determined at all the sampling points of the hot water system and at the spa pools. The presence of L. pneumophila serogroup 1 with the same molecular pattern as that found in the clinical isolate was confirmed in the hot water system (with a low proliferation risk according to legislation). The crude attack rate was 0.34% (95% CI 0.09–0.94). Samples without L. pneumophila were obtained only after structural changes were carried out. Possible factors participating in the cluster were water temperatures between 25°C and 30°C, stagnant water and early morning exposure (AU)
Assuntos
Texto completo: Disponível Coleções: Bases de dados nacionais / Espanha Contexto em Saúde: Agenda de Saúde Sustentável para as Américas / ODS3 - Saúde e Bem-Estar Problema de saúde: Objetivo 9: Redução de doenças não transmissíveis / Objetivo 8: Surtos, emergências e desastres / Meta 3.4: Reduzir as mortes prematuras devido doenças não transmissíveis Base de dados: IBECS Assunto principal: Legionelose / Água Estagnada / Legionella pneumophila Tipo de estudo: Estudo de etiologia / Estudo prognóstico / Fatores de risco Limite: Humanos Idioma: Espanhol Revista: Gac. sanit. (Barc., Ed. impr.) Ano de publicação: 2010 Tipo de documento: Artigo Instituição/País de afiliação: Direcció de Serveis de Vigilància Ambiental/España
Texto completo: Disponível Coleções: Bases de dados nacionais / Espanha Contexto em Saúde: Agenda de Saúde Sustentável para as Américas / ODS3 - Saúde e Bem-Estar Problema de saúde: Objetivo 9: Redução de doenças não transmissíveis / Objetivo 8: Surtos, emergências e desastres / Meta 3.4: Reduzir as mortes prematuras devido doenças não transmissíveis Base de dados: IBECS Assunto principal: Legionelose / Água Estagnada / Legionella pneumophila Tipo de estudo: Estudo de etiologia / Estudo prognóstico / Fatores de risco Limite: Humanos Idioma: Espanhol Revista: Gac. sanit. (Barc., Ed. impr.) Ano de publicação: 2010 Tipo de documento: Artigo Instituição/País de afiliação: Direcció de Serveis de Vigilància Ambiental/España
...