1.
Sci Rep ; 13(1): 12598, 2023 Aug 03.
Artigo em Inglês | MEDLINE | ID: mdl-37537262

RESUMO

In the parallel supply system of synchronous generator and virtual synchronous generator, the physical structure and control structure of the two kinds of power supply are quite different, and it is difficult to distribute the transient power of the two kinds of power supply evenly when the load changes abruptly. Especially in the case of sudden load increase, virtual synchronous generator bears too much load in the transient process because of its fast adjustment speed, and even causes short-term overload, which makes the capacity of virtual synchronous generator can not be fully utilized. In view of this problem, firstly, the mechanism of transient power uneven distribution of two heterogeneous power sources is explained from the differences of frequency modulation, voltage regulation and output impedance. Secondly, virtual speed regulation, virtual excitation and dynamic virtual impedance are added to the traditional virtual synchronous generator control to simulate the speed regulation characteristics and electromagnetic transient characteristics of the synchronous generator, so as to realize the transient and steady-state power equalization between heterogeneous power supplies when the virtual synchronous generator and the synchronous generator run in parallel. Thirdly, in order to ensure the fast dynamic response characteristics of the virtual synchronous generator in independent operation mode, the traditional virtual synchronous generator control algorithm is still maintained in independent operation mode, and the mode switching control link based on state tracking is designed to realize smooth switching between the two working modes. Finally, the hardware in loop experiment results based on RT-LAB show that the proposed control method can realize the transient and steady-state power equalization when the virtual synchronous generator and the synchronous generator operate in parallel, it can keep the fast voltage regulation and frequency modulation ability when the virtual synchronous generator operates independently, and can realize smooth switching between independent and parallel operation modes.

2.
Sci Rep ; 13(1): 15045, 2023 Sep 12.
Artigo em Inglês | MEDLINE | ID: mdl-37700158

RESUMO

Virtual synchronous generator (VSG) not only increases the inertia of grid-connected system, but also brings the problem of active power oscillation under grid disturbance. Therefore, VSG control strategy and system model order reduction method with transient electromagnetic power compensation are proposed. The closed-loop active power small signal model of the system is established, and the influence of transient electromagnetic power compensation on the power stability of VSG is analyzed based on root locus method. By removing the items which have little influence on the stability of the system in the small signal model, the order is reduced to obtain the equivalent second-order model of the system. According to the second-order model, the quantitative design criteria of the system parameters are given. The proposed transient electromagnetic power compensation strategy not only increases the transient equivalent damping of the system, but also does not affect the primary frequency modulation characteristics and will not cause large overshoot of the output active power. The experimental results are consistent with the theoretical analysis, which testify the effectiveness and correctness of the system control strategy and the model reduction method.

3.
Sci Rep ; 7(1): 9025, 2017 08 22.
Artigo em Inglês | MEDLINE | ID: mdl-28831139

RESUMO

This paper focus on the power fluctuations of the virtual synchronous generator(VSG) during the transition process. An improved virtual synchronous generator(IVSG) control strategy based on feed-forward compensation is proposed. Adjustable parameter of the compensation section can be modified to achieve the goal of reducing the order of the system. It can effectively suppress the power fluctuations of the VSG in transient process. To verify the effectiveness of the proposed control strategy for distributed energy resources inverter, the simulation model is set up in MATLAB/SIMULINK platform and physical experiment platform is established. Simulation and experiment results demonstrate the effectiveness of the proposed IVSG control strategy.