Pd/Ag coated fiber Bragg grating sensor for hydrogen monitoring in power transformers.
Ma, G M; Jiang, J; Li, C R; Song, H T; Luo, Y T; Wang, H B.
Afiliação
  • Ma GM; State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, People's Republic of China.
  • Jiang J; State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, People's Republic of China.
  • Li CR; State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, People's Republic of China.
  • Song HT; State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, People's Republic of China.
  • Luo YT; Electric Power Research Institute of Guangdong Power Grid Co., Ltd., Guangzhou 510080, People's Republic of China.
  • Wang HB; Electric Power Research Institute of Guangdong Power Grid Co., Ltd., Guangzhou 510080, People's Republic of China.
Rev Sci Instrum ; 86(4): 045003, 2015 Apr.
Article em En | MEDLINE | ID: mdl-25933889
ABSTRACT
Compared with conventional DGA (dissolved gas analysis) method for on-line monitoring of power transformers, FBG (fiber Bragg grating) hydrogen sensor represents marked advantages over immunity to electromagnetic field, time-saving, and convenience to defect location. Thus, a novel FBG hydrogen sensor based on Pd/Ag (Palladium/Silver) along with polyimide composite film to measure dissolved hydrogen concentration in large power transformers is proposed in this article. With the help of Pd/Ag composite coating, the enhanced performance on mechanical strength and sensitivity is demonstrated, moreover, the response time and sensitivity influenced by oil temperature are solved by correction lines. Sensitivity measurement and temperature calibration of the specific hydrogen sensor have been done respectively in the lab. And experiment results show a high sensitivity of 0.055 pm/(µl/l) with instant response time about 0.4 h under the typical operating temperature of power transformers, which proves a potential utilization inside power transformers to monitor the health status by detecting the dissolved hydrogen concentration.