Legionella monitoring results by water quality characteristics in a large public water system.
Gleason, Jessie A; Newby, Robert; Gaynor, John J; Lee, Lee H; Chu, Tinchun; Bliese, Alorah D; Taylor, Calvin W; Yoon, Paul; DeLorenzo, Suzanne; Pranitis, David; Bella, Joe.
Afiliação
  • Gleason JA; Environmental and Occupational Health Surveillance Program, New Jersey Department of Health, 135 East State Street, P.O. Box 369, Trenton, NJ, 08625, USA. Jessie.gleason@doh.nj.gov.
  • Newby R; Division of Science, New Jersey Department of Environmental Protection, 428 East State Street, P.O. Box 420, Trenton, NJ, 08625, USA.
  • Gaynor JJ; Department of Biology, Montclair State University, Montclair, NJ, 07043, USA.
  • Lee LH; Department of Biology, Montclair State University, Montclair, NJ, 07043, USA.
  • Chu T; Department of Biological Sciences, Seton Hall University, 400 South Orange Ave, South Orange, NJ, 07076, USA.
  • Bliese AD; Department of Biology, Montclair State University, Montclair, NJ, 07043, USA.
  • Taylor CW; Department of Biology, Montclair State University, Montclair, NJ, 07043, USA.
  • Yoon P; Department of Biological Sciences, Seton Hall University, 400 South Orange Ave, South Orange, NJ, 07076, USA.
  • DeLorenzo S; Passaic Valley Water Commission, 1525 Main Avenue, Totowa, NJ, 07512, USA.
  • Pranitis D; Passaic Valley Water Commission, 1525 Main Avenue, Totowa, NJ, 07512, USA.
  • Bella J; Passaic Valley Water Commission, 1525 Main Avenue, Totowa, NJ, 07512, USA.
Environ Sci Pollut Res Int ; 30(19): 55974-55988, 2023 Apr.
Article em En | MEDLINE | ID: mdl-36913019
ABSTRACT
Legionella, the causative agent of Legionnaires' disease, is an emerging concern for water utilities. Passaic Valley Water Commission (PVWC) is a public drinking water supplier, which provides treated surface water to approximately 800,000 customers in New Jersey. To evaluate the occurrence of Legionella in the PVWC distribution system, swab, first draw, and flushed cold water samples were collected from total coliform sites (n = 58) during a summer and winter sampling event. Endpoint PCR detection methods were combined with culture for Legionella detection. Among 58 total coliform sites during the summer, 17.2% (10/58) of first draw samples were positive for 16S and mip Legionella DNA markers and 15.5% (9/58) in flushed samples. Across both summer and winter sampling, a total of four out of 58 sites had low-level culture detection of Legionella spp. (0.5-1.6 CFU/mL) among first draw samples. Only one site had both a first and flush draw detection (8.5 CFU/mL and 1.1 CFU/mL) for an estimated culture detection frequency of 0% in the summer and 1.7% in the winter among flushed draw samples. No L. pneumophila was detected by culture. Legionella DNA detection was significantly greater in the summer than in the winter, and detection was greater in samples collected from areas treated with phosphate. No statistical difference was found between first draw and flush sample detection. Total organic carbon, copper, and nitrate were significantly associated with Legionella DNA detection.
Assuntos
Palavras-chave

Texto completo: 1 Coleções: 01-internacional Base de dados: MEDLINE Assunto principal: Legionella / Doença dos Legionários / Legionella pneumophila Limite: Humans Idioma: En Ano de publicação: 2023 Tipo de documento: Article

Texto completo: 1 Coleções: 01-internacional Base de dados: MEDLINE Assunto principal: Legionella / Doença dos Legionários / Legionella pneumophila Limite: Humans Idioma: En Ano de publicação: 2023 Tipo de documento: Article