RESUMEN

Introducción:

Esta investigación plantea una propuesta de rediseño para el sistema de distribución de vapor y de retorno de condensado en el área de lavandería del hospital. Materiales y

Métodos:

En el desarrollo del proyecto se realizó el levantamiento de información que comprende los diferentes requerimientos de los equipos de consumo de vapor, trazado de la tubería del sistema actual y deficiencias energéticas.

Resultados:

Para el rediseño se implementaron conexiones superiores a los equipos, piernas colectoras y finales de línea, garantizando así que no ingrese condensado a los equipos y que no afecte a la tubería por el golpe de ariete. El condensado drenado de las líneas de vapor y a la salida de los arreglos de trampeo de los equipos de consumo, antes de dirigirse al tanque de condensado, pasa por un tanque de revaporizado donde se obtiene revaporizado a baja presión, el mismo que puede ser utilizado en otro proceso con estos requerimientos.

Discusión:

Se determinó el costo del proyecto y se realizó un análisis económico, tomando en cuenta el ahorro energético-económico que se obtendrá con la implementación del rediseño, así como la reducción en las emisiones de CO2. Palabras clave Tuberías, vapor, lavandería.
ABSTRACT

Introduction:

This research proposes to redesign the steam distribution and condensate return systems in the hospital laundry area.

Methods:

During the project development, we gather information from steam consumer equipment, piping layout of the current system and energy deficiencies.

Results:

For the redesign, it has been implemented upward connections to equipment, drain pockets and line endings, thus, guarantying that condensate does not get into the laundry equipments and pipes to avoid being damaged by the water hammer. The drained condensate from the steam lines, before being trapped in the tank of condensate, is conducted to a flash tank creating a low-pressure flash steam that can be used in other process with these requirements.

Discusion:

The cost of the project was obtained and an economic analysis was undertaken bearing in mind the energy and economic saving that will be obtained with the redesign as well as the CO2 emissions reduction.
Assuntos

Texto completo: Disponível Coleções: Bases de dados internacionais Base de dados: LILACS Assunto principal: Vapor / Tubulações / Consumo de Energia / Serviço Hospitalar de Lavanderia Idioma: Espanhol Revista: Cambios rev. méd Assunto da revista: Medicina / Saúde Pública Ano de publicação: 2017 Tipo de documento: Artigo País de afiliação: Equador Instituição/País de afiliação: Escuela Politécnica Nacional/EC
Texto completo: Disponível Coleções: Bases de dados internacionais Base de dados: LILACS Assunto principal: Vapor / Tubulações / Consumo de Energia / Serviço Hospitalar de Lavanderia Idioma: Espanhol Revista: Cambios rev. méd Assunto da revista: Medicina / Saúde Pública Ano de publicação: 2017 Tipo de documento: Artigo País de afiliação: Equador Instituição/País de afiliação: Escuela Politécnica Nacional/EC
...