Determination of Fire Parameters of Polyamide 12 Powder for Additive Technologies.
Kuracina, Richard; Szabová, Zuzana; Buranská, Eva; Pastierová, Alica; Gogola, Peter; Buranský, Ivan.
Afiliação
  • Kuracina R; Institute of Integral Safety, Faculty of Materials Science and Technology in Trnava, Slovak University of Technology in Bratislava, Ul. Jána Bottu 2781/25, SK-917 24 Trnava, Slovakia.
  • Szabová Z; Institute of Integral Safety, Faculty of Materials Science and Technology in Trnava, Slovak University of Technology in Bratislava, Ul. Jána Bottu 2781/25, SK-917 24 Trnava, Slovakia.
  • Buranská E; Institute of Integral Safety, Faculty of Materials Science and Technology in Trnava, Slovak University of Technology in Bratislava, Ul. Jána Bottu 2781/25, SK-917 24 Trnava, Slovakia.
  • Pastierová A; Institute of Integral Safety, Faculty of Materials Science and Technology in Trnava, Slovak University of Technology in Bratislava, Ul. Jána Bottu 2781/25, SK-917 24 Trnava, Slovakia.
  • Gogola P; Institute of Materials, Faculty of Materials Science and Technology in Trnava, Slovak University of Technology in Bratislava, Ul. Jána Bottu 2781/25, SK-917 24 Trnava, Slovakia.
  • Buranský I; Institute of Materials, Faculty of Materials Science and Technology in Trnava, Slovak University of Technology in Bratislava, Ul. Jána Bottu 2781/25, SK-917 24 Trnava, Slovakia.
Polymers (Basel) ; 13(17)2021 Sep 06.
Article em En | MEDLINE | ID: mdl-34503053
ABSTRACT
The use of additive technologies keeps growing. Increasingly, flammable powder materials are also used in additive technologies, and there is a risk of explosion or fire when using them. The current article deals with the determination of fire parameters of a powder sample of polyamide Sinterit PA12 Smoth in accordance with the EN 14034 and EN ISO/IEC 80079-20-2 standards. For that purpose, a sample at a median size of 27.5 µm and a humidity of 0% wt. was used. The measurements showed that the maximum explosion pressure of the PA12 polyamide sample was 6.78 bar and the value of the explosion constant Kst was 112.2 bar·m·s-1. It was not possible to determine the MIT value of the settled dust, since the melting point of polyamide sample is low. The MIT of the dispersed dust was 450 °C. Based on the measured results, it can be stated that the powdered polyamide PA12 poses a risk in terms of explosions and fires. Therefore, when using polyamide PA12 in additive technologies, it is necessary to ensure an effective explosion prevention.